Poles | 1P+N |
Sensitivity | 300MA |
Compliance with standards | EN 61009 |
Compliance with standards | IEC 61009 |
Tripping curve | Curve B: the magnetic tripping devices act at between 3 and 5 In |
Tripping curve | Curve C: the magnetic tripping devices act at between 5 and 10 In |
Mechanical endurance (Number of O/C cycles) | 20000 |
Environment | Setting temperature for ratings 6 to 40 A (30°C) |
Electrical endurance under rated current (Number of O/C cycles) | 20,000 =< 20 A |
Electrical endurance under rated current (Number of O/C cycles) | 10,000 =< 25 A |
Rated breaking capacity (Icn) | 6,000 A |
Rated residual breaking and making capacity (IDm) | 6,000 A |
Storage temperature | –40°C…+70°C |
IP degree of protection | IP4/IPxxD for the part outside of the enclosure |
Insulation voltage (Ui) | 400 V |
Rated impulse withstand voltage (Uimp) | 4 kV |
Service temperature | Type AC: from -5°C to +60°C |
Service temperature | Type A and type A-si: from -25°C to +60°C |
8/20 μs impulse withstand | 250 A |
Limitation class | 3 |
Insulation class | 2 |
Tropicalization | Treatment 2 (relative humidity 95% at 55°C) |