Rated Voltage | 110 V a.c / 220 V a.c, 60 Hz |
Permissible Voltage Fluctuation Range | Rated Voltage ± 10% |
Consumption Power | Approx. Max 3 VA |
Input | Thermocouple, Resistive, d.c Current, d.c Voltage(see Standard Range Code)(Built - in Burnout circuit) |
Adjusting Sensitivity | ±0.2%(fixed) of Max. Range |
Control Method | Proportional Control, ON / OFF Control |
Setting Method | Analog Setting |
Display Method | Analog Display |
Control Output | Relay output : Capacity 250 V a.c 3 A (Resistive Load) contact : 1c | SSR Output : 12 V a.c (Constant Voltage Pulse) (Resistive Load : above 800 Ω) | Current Output : 4 - 20 mA d.c (Resistive Load : below 600 Ω) |
|
Setting accuracy | 2 % of Max. Range |
Display accuracy | Below ±2.0 % of Max. Range |
Alarm Operation | High Limit Operation, Low Limit Operation, High / Low Limit Operation |
Proportional Band | 1 ~ 10 % of Max. Range(variable) | 1 ~ 3 % of Max. Range(variable) | 3 % of Max. Range(fixed) |
Proportional Cycle | Relay Output : 20 ~ 30 sec / SSR Output : 2 ~ 4 sec |
Insulation Resistance | Above 100 MΩ (500 V a.c mega) |
Dielectric Strength | 2000 V a.c 50 ~ 60 Hz for 1 minute |
Noise Immunity | Squared wave noise(pulse width : 1000 μs) ±1 KV |
Vibration Resistance | 10 - 50 Hz (cycle for 1 minute), double amplitude : 0.75 mm, each X Y Z direction for 1 hour |
Shock | 300 m/s² (approx. 30G) |
Relay Life Expectancy | Mechanical : above 10 millions times Electrical : above 100 thousands times (250 V a.c, 3 A Resistive Load) |
Operating Ambient Temperature / Humidity | 0 ~ 50 °C, 35 ~ 85 % R.H. (without condensation) |