| Poles | 3P+N+G |
| Surge arrester type | Electrical distribution network |
| Maximum discharge current Imax | 40 kA |
| Nominal frequency fN | 50/60Hz |
| Surge arrester class type | Type 2 |
| Nominal voltage Un | 400/415 VAC |
| Nominal voltage Un | 240 V AC (230/400 V AC ... 240/415 V AC) |
| Compliance with standards | Product standard: EN 61643-11 Type 2 IEC 61643-1 T2 |
| [Iimp] impulse current | 12 kA (N-PE) (10/350) μs |
| [Iimp] impulse current | 20 kA (L-N) (8/20) μs |
| [Up] voltage protection level | 1.5 kV type 1 common mode N/PE |
| [Up] voltage protection level | 1.5 kV type 1 differential mode L/N |
| [Uc] maximum continuous operating voltage | 335 V AC (L-N) |
| [Uc] maximum continuous operating voltage | 260 V AC (N-PE) |
| Nominal discharge current In | 20 kA (8/20) µs (L-N) |
| Nominal discharge current In | 20 kA (8/20) µs (N-PE) |
| [If] follow current | 0.1 kA common mode N/PE |
| IP degree of protection | IP20 |
| Mounting type | 35 mm symmetrical DIN rail |
| Color | Màu xám |
| Material | Housing material: PBT |
| Response time | ≤ 100 ns (L-PE) |
| Environment | -40 °C ... 80 °C |