| Built-in PID auto tuning function | ㆍSetting data lock function | | ㆍDirect/Reverse operation selection function | ㆍInput compensation function | | ㆍAlarm (ALH, ALL, LBA) | ㆍDecimal point display function | | ㆍUpper/Lower limit setting limitation function | |
|
| Power Voltage | 100 - 240 V a.c, 50 - 60 ㎐ (voltage fluctuation rate : ± 10 %) |
| Power Consumption | Below approx. 11 VA |
| Input | | ㆍThermocouple : K, J, E, T, R, B, S, L, N, U, W | | ㆍRTD : D(Kpt), P(Dpt) ㆍd.c Voltage Current input : 1 ~ 5 V d.c, 0 ~ 10 V d.c |
|
| Control Output | ㆍRelay : 250 V a.c 3 A (resistive load) ㆍSSR : 12 V d.c pulse voltage(above resistive load 800 Ω) ㆍCurrent Output : 4 - 20 mA d.c |
Adjusting Operation Alarm Output | | (Below Resistive load 600 Ω) | | ㆍPID operation ㆍON/OFF operation |
|
| Loop Break Alarm | Relay output : ALH, ALL (250 V a.c 3 A) |
| Setting Method | Relay output : LBA (250 V a.c 3 A) |
| Indicator Method | Digital Setting by Up/Down Keys |
| Accuracy | Digital display (PV : red, SV : red) |
| Power failure back up | ±0.5 % of F.S (But thermocouple Btype 0 ~ 400 ˚C out of guarantee range) |
| Dielectric Strength | Semipermanent |
| Vibration | Malfunction | 2000 V a.c, 50/60 ㎐, for 1 minute (between the terminals of the two-polar current carry part) |
| Durability | 2 - 55 ㎐ each X · Y · Z direction for 10 minutes |
| Shock | Malfunction | 10 - 55 ㎐, 0.76 mm, each X · Y · Z direction for 2 hours |
| Durability | 100 ㎨ 3 times at each 6 direction (approx. 10 G) |
| Life | Malfunction | 300 ㎨ 3 times at each 6 direction (approx. 30 G) |
| Electrical | Above 10 million times (Relay type) |
Operating Ambient Temperature/Humidity | | Above 300 thousand times (Relay type) | | 0 ~ 50 ˚C / 35 ~ 85 % R.H. (without condensation) |
|